The HIMA X-DI3205 (985210231) is a SIL 3-certified digital input module for the HIMax safety system, designed for critical shutdown applications. It features 32 galvanically isolated channels (24V DC) with fault detection (open-circuit/short-circuit) and meets IEC 61508 standards. Its hot-swappable design ensures continuous operation in hazardous industries like oil/gas and power generation.
Key Identification & Compliance
-
Model: X-DI3205 (Order No. 985210231)
-
System Compatibility: HIMA HIMax Safety PLCs
-
Safety Certification: SIL 3 (IEC 61508), TÜV-approved
Technical Parameters
-
Input Channels: 32 channels (individually configurable)
-
Input Type: 24V DC (sink/source)
-
Voltage Range: 15–30V DC
-
Current Consumption: 3mA per channel (typical)
-
-
Isolation:
-
Channel-to-channel & system isolation (1500V AC)
-
Group isolation (8 channels per group)
-
-
Response Time: <1ms per channel
Functional Features
-
Diagnostics:
-
Open-circuit, short-circuit, and overload detection
-
Per-channel LED status (green/red)
-
-
Redundancy: Hot-swappable (supports online maintenance)
-
Wet Contact Support: Compatible with NAMUR sensors (optional).
Environmental & Mechanical
-
Operating Temperature: -40°C to +70°C
-
Humidity: 5–95% (non-condensing)
-
Vibration/Shock: IEC 60068-2-6/27 (industrial grade)
-
Protection Class: IP20 (panel-mounted)
Certifications & Approvals
-
Functional Safety: SIL 3 (IEC 61508), TÜV Rheinland
-
EMC: EN 61326-1 (industrial immunity)
-
Hazardous Areas: ATEX/IECEx (optional)
Integration & Configuration
-
Wiring: Spring-clamp terminals (screwless, 0.2–2.5mm²)
-
Software: Configured via HIMA Safety Manager (HSM)
-
MTBF: >150,000 hours (predicted)
Critical Notes
-
Safety Constraints: Requires HIMA-approved configuration tools for SIL 3 compliance.
-
Replacement: Use exact part number (985210231) to maintain safety integrity.












Reviews